3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
18
Siemens · 2012
Measurement method
Vectorial summation current formation (measurement method 1)
The three phase currents and the N conductor current are mea-
sured directly.
The electronic release determines the ground-fault current by
means of vectorial summation current formation for the three
phase currents and the N conductor current.
Direct measurement of the ground-fault current (measurement
method 2)
A standard current transformer with the following data is used for
measurement of the ground-fault current:
1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker
is 0.11
Ω
). The current transformer can be installed directly in the
grounded neutral point of a transformer.
3-pole circuit breakers, current transformers in the N conductor
3-pole circuit breakers, current transformers in the grounded neutral
point of the transformer.
4-pole circuit breakers, current transformers in the grounded neutral
point of the transformer.
Setting
How the module is set depends on the measurement method
used (see above):
Measurement method 1: in position .
Measurement method 2: in position .
This setting can be implemented for the electronic release ver-
sion ETU76B with Menu/Comm.
Ground-fault protection with
I
2
t characteristic curve
With the exception of the ETU27B electronic release, all
versions of the ground-fault modules are supplied with an
I
2
t
characteristic curve which can be activated.
Selection criteria for 3WL circuit breakers
Basic criteria for selecting circuit breakers are:
Max. short-circuit current
at place of installation of circuit
breaker
I
k max
.
This value determines the short-circuit breaking capacity or
short-circuit current carrying capacity of the circuit breaker.
It is compared with the value
I
cu
,
I
cs
,
I
cw
of the circuit breaker
and essentially determines the size of the circuit breaker.
See illustration "Overview of 3WL Circuit Breakers/Non-Auto-
matic Air Circuit Breakers".
Rated current
I
n
which is to flow through the branch circuit.
This value must not be greater than the maximum rated circuit
breaker current of the circuit breaker.
The rated current for the 3WL circuit breaker is specified using
the rated current module. See illustration "Overview of 3WL
Circuit Breakers/Non-Automatic Air Circuit Breakers" in "De-
sign".
Ambient temperature
for the circuit breaker.
This is usually the control cabinet internal temperature.
•Design
of the circuit breaker
Minimum short-circuit current
which flows through the switching device. The release must
still detect this value as a short-circuit and must respond by
tripping.
Protection functions
of the circuit breaker.
These are determined by the selection of the
corresponding electronic release, see the table
"Functions of the Electronic Releases" under "Functions".
NSE 00946
L1
L2
L3
N
PE
T5
SENTRON WL
NSE 00947
L1
L2
L3
N
PE
T6
SENTRON WL
T6: 1200 A/1 A
NSE 00948
L1
L2
L3
N
PE
T6
SENTRON WL
T6: 1200 A/1 A
© Siemens AG 2011